bayfront1-resized-600

BAYFRONT AT A GLANCE

  • 480-bed private hospital
  • 75,000 ft2
  • Over 3,000 employees
  • (4) York chillers
  • 2,575 tons installed cooling capacity

APPROACH

  • Convert plant to Integrated Primary/Secondary® design
  • Reconfigure tertiary pumps to alleviate system pressure problems and eliminate wasted energy
  • Add VFDs to all building pumps to eliminate wasted pump energy
  • Design and install PLC based adaptive control algorithms to ensure maximum chiller loading, optimal control of all CHW pumps and proper balance of cooling towers and chillers

IMPLEMENTATION

  • CEO ® system connected directly to JCI Metasys system via BACnet IP protocol, allowing tekWorx to gather real-time data on temperatures, flows, etc., and to fully control all plant equipment
  • Failover sequence developed and implemented to address control redundancy
  • No plant downtime during the course of this project
  • All major equipment remained in operation during commissioning

RESULTS

  • Manually operated system operating at 1.1kW/ton is now a real-time adaptive control system operating at .75 kW/ton
  • System experiences much less wear and tear
  • Operators are now freed up to perform other important tasks
  • CEO® User Interface has provides the staff with better insight into the system for diagnostics and trouble shooting