Chilled Water Plant Optimization Cuts Hospital’s Annual Energy Costs 30%

Performance contract enables hospital to recover lost cooling capacity and cut costs 30% with tekWorx innovative hydronic design and adaptive control strategy.

Facility Bio

  • Rockville, MD
  • 313 bed hospital with Acute Care Center
  • 500,000 ft² facility
  • Four (4) Trane chillers
  • 3,700 tons installed cooling capacity

Situation

  • Healthcare system energy reduction initiative for all sites
  • Primary-Secondary-Tertiary system with inherent inefficiencies
  • High system pressure
  • Low CHW ΔT
  • High kW/ton
  • Ineffective building pump control required manual intervention
  • Andover BAS with standard sequence, no optimization

Solution

  • Convert plant to Integrated Primary-Secondary® design to eliminate bypass
  • low and blending, raise ΔT
  • Install VFDs on 3 of 6 primary CHW pumps
  • Control tertiary pumps to reduce system pressure and wasted energy
  • Install adaptive Control Engine Optimization® solution to continuously minimize kW/ton

Results That Exceed Client Expectations

Financial Savings

  • $140,000 utility rebate
  • $87,400 in annual energy savings

Energy Impact

  • 760,000 kWh saved annually
  • .31 kW/ton energy efficiency improvement

Operational Benefits

  • System experiences much less wear and tear
  • Reduced manual intervention
Still Have Questions?

Start saving on cooling costs.

Calculate your savings instantly

We are the chilled water plant optimization experts

tekWorx optimization solutions consistently save hospitals and healthcare facilities 20-40% in annual energy costs. We'd love to help your facility do the same. Get in touch!

Approachable Expertise ®
4538 Cornell Road
Cincinnati, Ohio 45241
1-513-533-4777
[email protected]
© 2020 tekWorx. All right reserved. Privacy Policy