Chilled Water Plant Optimization Cuts Hospital’s Annual Energy Costs 30%
Performance contract enables hospital to recover lost cooling capacity and cut costs 30% with tekWorx innovative hydronic design and adaptive control strategy.


Facility Bio
- Rockville, MD
- 313 bed hospital with Acute Care Center
- 500,000 ft² facility
- Four (4) Trane chillers
- 3,700 tons installed cooling capacity

Situation
- Healthcare system energy reduction initiative for all sites
- Primary-Secondary-Tertiary system with inherent inefficiencies
- High system pressure
- Low CHW ΔT
- High kW/ton
- Ineffective building pump control required manual intervention
- Andover BAS with standard sequence, no optimization

Solution
- Convert plant to Integrated Primary-Secondary® design to eliminate bypass low and blending, raise ΔT
- Install VFDs on 3 of 6 primary CHW pumps
- Control tertiary pumps to reduce system pressure and wasted energy
- Install adaptive Control Engine Optimization® solution to continuously minimize kW/ton
Results That Exceed Client Expectations

Financial Savings
- $140,000 utility rebate
- $87,400 in annual energy savings

Energy Impact
- 760,000 kWh saved annually
- .31 kW/ton energy efficiency improvement

Operational Benefits
- System experiences much less wear and tear
- Reduced manual intervention
Still Have Questions?
Start saving on cooling costs.
Calculate your savings instantlyWe are the chilled water plant optimization experts
tekWorx optimization solutions consistently save faciliites 20-40% in annual energy costs. We'd love to help your facility do the same. Get in touch!

Approachable Expertise ®
© 2020 tekWorx. All right reserved. Privacy Policy