| |
|
Adaptive
Control: Continuous, Real-Time Energy Optimization to Save
Energy and Money! |
|
Real energy optimization requires a control strategy to deal with
the continually changing real world conditions in your HVAC system. tekWorx meets this challenge head on by applying its proven adaptive
control techniques your system - NO canned BAS programs or equipment
vendor sequences that just deal with the chiller. A closer look at
tekWorx' distribution pump control illustrates how adaptive control
saves money.
|
Using design parameters (flow, head, friction loss), tekWorx generates
a Pump kW Consumption Analysis for each specific system, similar to the example shown
(left). The curves illustrate the point above which the kW required to operate one
pump is actually more than that required for two pumps to deliver the same flow.
The corresponding kW value is loaded in the control program and used to sequence
ON / OFF the lag pump in the initial operation. The adaptive control
algorithm then analyzes the actual system behavior during each sequence operation,
and makes an on-line adjustment to the sequence point for the following operation.
The result is that the optimize setpoint is continuously used, thus dramatically
reducing pump energy consumption.
The Pump kW Consumption Analysis tool, in conjunction with the
adaptive control techniques provide one other benefit that saves
both cost and operating expense. Design engineers can accurately
select the minimum size distribution pumps to safely get the job
done.
One significant yet hidden benefit: the adaptive algorithm assures that
pumps always operate in the eye of their efficiency curve, thereby reducing
radial stress. By eliminating this major cause of seal wear, maintenance
costs are greatly reduced.
|
|
|
Variable
Primary Pumping |
|
Advances in chiller design and digital
control technology in the past few years have caused a fundamental
shift toward Variable Primary (VP) design for distribution pumping,
and there are now thousands of successful VP installations. VP's
proven reliability, energy savings and ability ot maximize plant
capacity have rendered the venerable Primary/ Secondary method (P/S)
obsolete. A comparison of the two designs readily shows why.
P/S
Basics P/S system (shown at the left) consists of two pumping
loops that share a common pipe. The primary loop (also known as the
production loop) uses constant speed pumps to circulate a fixed
volume of water through the chillers. The secondary loop (also
referred to as the distribution loop.) uses variable speed pumps to
deliver the required volume of water to satisfy the load. The volume
of water is regulated by the speed of the secondary pumps which is
controlled to maintain the remote
P setpoint. This
arrangement allows a constant volume of water to be circulated
through the chillers, while the flow through the common pipe varies
in relation to the flow required to satisfy the load. Thus, at a
light load, the low pump secondary speed means that a high volume of
water is bypassed back to the chiller; very little water bypassed at
a high load because the high secondary pump speed draws most if not
all of the water off the primary loop and sends it to the load.
While this system "works" to produce cooling, the system
T varies with the
amount of water being bypassed, and the energy energy performance
and available capacity varies with it.
VP Basics In contrast, the VP
design (shown at the right) has only one loop, so it uses only one
set of variable speed pumps to circulate water through both the
chillers and the load. The pump speed is still regulated to maintain
the remote
P setpoint
(just like the P/S system.) The VP system has a control valve
in the bypass line that opens during light load conditions to insure
minimum evaporator flow. When this valve is closed (which is most of
the time) there is no flow through the common pipe, and thus there
is no negative impact on DT.
Summary of Variable Primary
Benefits
-
Superior energy
performance - less pump energy, no negative impact on
T
-
Full Use of
Capacity: efficient chiller loading.
-
Low
first
cost: fewer pumps, less piping, simpler electrical installation
-
Small physical
space more productive usable/rentable space
-
Flexibility /
Backup Pumps and chillers are headered, so that any pump can run
with any chiller
-
Reliability and
Maintenance less equipment mess less equipment failure.
|
|
 |
| |
|
Delta-T
Compensation for Chiller Staging |
|
|
|
Condenser Water Optimization |
This adaptive control technique yields the optimum condenser water
temperature for the current cooling load and operating conditions.
The algorithm continuously balances the energy associated with a higher
cooling tower fan speed against the corresponding increase in chiller
efficiency afforded by a lower condenser water temperature. Thus, the chiller
continuously operates at the optimum condenser water temperature,
which directly translates into big energy savings.
|
|
|